Heat exhaust ventilators – Testing for resistance to wind load, air permeability, upwards and downwards loading, water t
Testing for wind load, air tightness and rain tightness is part of extensive testing of the fire ventilator aiming at certification. Other parts of RISE are tests for fire resistance, snow load, opening/closing test and vibration test.
Purpose/Benefit:The following tests are offered: air tightness, rain tightness and wind load
Testing of function and safety during use.
Method (what/which methods are used to perform the service):Safety against wind load according to EN12101-2, Annex F static load of the ventilator with 10 kg soft weight bags on the inside of the ventilator with the inverted upside down, and applies to the ventilator of magnitude on long side even 3 m.
Air tightness, rain tightness and wind load according to EN 1873 and EN 14963 testing of the ventilator mounted on a horizontal airtight platform
Delivery (what does the client get after performed service – e.g. a report, certificate etc.):Delivery time will be given on request of a quote
Area: Construction Contact person (Enter one name per field. Activated personal contact pages will appear automatically):Richard Dawson, Teknologie magister
Pontus Randén, Gruppchef
Any required preparatory work will be advised on request of a quote
Standards:EN12101-2 Annex F
EN 1873
EN 14963
Certification and marking: Not applicable Type of service: Not applicable Instrument: Not applicable General area: Not applicable Order information: Quote inquiries and order confirmations can be taken via E-mail or by telephone Divison (OLD): Do not use - Division Built Environment Delivery level: Not applicableMetrology
Construction Tjänstetyp tagg: Provning