Fire test according to IMO 2010 FTP Code Part 1
IMO 2010 FTP Code Part 1 - International Code for Application of Fire Test Procedures, 2010
This service is also relevant in: Metrology, Maritime, Materials and durability
Service details
- Service
- Fire test according to IMO 2010 FTP Code Part 1
- Delivery level
- Accredited
- Standards
Similar test methods: EN ISO 1182
- Price
- Price on tender
- Preparations
Material consumption of homogeneous Products during test:
- Complete test: 12 test specimens, cylindrical with the diameter 45 mm and height 50 mm.
- Indicative test: 2 test specimens, cylindrical with the diameter 45 mm and height 50 mm
Material consumption of non-homogeneous Products during test:
- Complete test: 24 test specimens, cylindrical with the diameter 45 mm and height 50 mm.
- Indicative test: 8 test specimens, cylindrical with the diameter 45 mm and height 50 mm
If the thickness of the product is thinner than 50 mm sufficient number of horizontal layers of the material shall be used to adjust the thickness to 50 mm.
- Order
Before testing we ask you to fill in the Order Specification Form and attach your order.
Order Specification Form
Purpose
This fire test is for identification of products which produce only a very limited amount of heat and flame when exposed to temperatures of approximately 750º C. The main purpose of the test is to determine the non-combustibility of products for maritime use.
Products and materials for maritime use is fire tested according to the International Maritime Organization (IMO) code, IMO 2010 FTP Code. The results from fire testing according to the FTP-code can be used as a basis for type approval (also called the wheel mark).
Type approval is regulated in accordance with European Parliament Directive 2014/90/EU. RISE can perform the fire tests, issue the certificates and perform the production control required in order to gain the wheel mark.
Method
First the organic content of the product is determined. After, a test specimen is located inside a cylindrical furnace tube at 750 °C. The furnace and specimen temperatures are measured continuously during the test. Potential combustion of the test specimen is registered as temperature rise and/or visible flames. Mass loss of the test specimen is calculated after the test. These parameters are used to decide if the product is non-combustible or not.
Deliveries