Field sampling testing of sprinklers
RISE is offering field sampling testing of sprinklers in accordance with Annex K of EN 12845:2015+A1:2020 and the requirements in NFPA 25
This service is also relevant in: Metrology, Construction
Service details
- Service
- Field sampling testing ("25-year inspection") of sprinklers
- Standards
EN 12845:2015+A1:2020
NFPA 25
SP Metod 4353:2018
- Price
Current prices are given in the form field under the heading Request for quote.
- Preparations
None.
- Request for quote
Additional information and prices are given in the form "Field sampling testing of sprinklers" that can be downloaded here.
Purpose
Annex K, ”Twenty‑five year inspection” of EN 12845:2015+A1:2020, ”Fixed firefighting systems – Automatic sprinkler systems – Design, installation and maintenance”, requires that a number of sprinklers should be removed and inspected no later than 25 years after their installation.
The testing indicates wheter the sprinklers in the actual system are serviceable or not.
Method
The sprinklers are evaluated regarding the following:
a) operation;
b) operation temperature;
c) variation of K-factor;
d) spray obstacles;
e) lodgement;
f) thermal sensitivity.
Annex K of SS-EN 12845:2015+A1:2020 stipulate how many sprinklers that should be tested, but the sample should at least include 20 sprinklers. Note that RISE Fire Research only tests the actual sprinklers. Malfunction of the system may involve other parts of the system such as the pipe or the water supply. That is not taken into consideration in these tests
Deliveries
The tests are reported in a report in English.